PTE-100-C |
PTE-50-CE |
PTE-100-V |
PTE-300-V |
PTE-50-CET |
UNO |
PTE-100-V
PTE-100-C |
PTE-300-V
PTE-50-CE |
PTE-300-V
PTE-100-C |
PTE-50-CET
PTE-100-V |
TRES |
| Number of output channels |
1 |
1 |
1 |
2 |
2 |
3 |
3 |
4 |
4 |
4 |
6 |
| Reversible Outputs (voltage or current) |
X |
X |
X |
X |
X |
X |
X |
X |
X |
X |
X |
| Maximum voltage outputs |
1 |
1 |
1 |
3 |
3 |
2 |
2 |
4 |
4 |
4 |
6 |
| Maximum current output |
1 |
1 |
1 |
3 |
3 |
2 |
2 |
4 |
4 |
4 |
6 |
| Maximum voltage reached |
250 V |
150 V |
300 V |
300 V |
150 V |
300 V |
300 V |
300 V |
300 V |
300 V |
300 V |
| Maximum current reached |
250 A |
50 A |
8 A |
8 A |
50 A (150 A with 3 channels in paralel) |
50 A |
250 A |
50 A |
250 A |
50 A (150 A with 3 channels in paralel) |
50 A (150 A with 3 channels in paralel) |
| Possibility of external frequency and phase synchronization |
— |
X |
X |
X |
X |
X |
Only
PTE-100-V |
X |
Only
PTE-300-V |
X |
X |
| Isolated outputs |
X |
X |
X |
X |
X |
X |
X |
X |
X |
X |
X |
| Manual Control |
X |
X |
X |
X |
X |
X |
X |
X |
X |
X |
X |
| Software Control |
X |
X |
X |
X |
X |
X |
X |
X |
X |
X |
X |
| Output power per phase |
1000 VA |
100 VA |
100 VA |
100 VA |
100 VA (300 VA with PTE-SER option) |
100 VA |
100 VA |
100 VA |
100 VA |
100 VA (300 VA with PTE-SER option) |
100 VA (300 VA with PTE-SER option) |
| Harmonic Generator |
— |
Up to7th |
Up to7th |
Up to7th |
Up to7th |
Up to7th |
Up to7th |
Up to7th |
Up to7th |
Up to7th |
Up to7th |
| Frequency Gererator |
— |
— |
40-420 Hz |
40-420 Hz |
— |
40-420 Hz |
40-420 Hz |
40-420 Hz |
40-420 Hz |
40-420 Hz |
40-420 Hz |
| Reproductor of faults and transients |
— |
— |
— |
— |
— |
X |
— |
— |
— |
— |
X |
| Simulation of dynamic faults manually |
— |
X |
X |
X |
X |
X |
Only
PTE-100-V |
X |
Only
PTE-300-V |
X |
X |
| Simulation of Frequency Ramping manually |
— |
— |
X |
X |
— |
X |
Only
PTE-100-V |
X |
Only
PTE-300-V |
X |
X |
| Auxiliary AC Voltage Output |
X |
X |
X |
X |
X |
X |
X |
X |
X |
X |
X |
| Auxiliary DC Voltage Output |
X |
(with PTE-FCG option) |
(with PTE-FCG option) |
(with PTE-FCG option) |
(with PTE-FCG option) |
(with PTE-FCG option) |
X |
(with PTE-FCG option) |
X |
X |
X |
| Number of Inputs |
1 |
2 |
1 |
1 |
2 |
3 |
2 |
3 |
2 |
2 |
3 |
| Phase Angle Range |
0-180º (with PTE-FCC option) |
0-360º |
0-360º |
0-360º |
0-360º |
0-360º |
0-360º |
0-360º |
0-360º |
0-360º |
0-360º |
| Phase Angle Resolution |
0,2º (with PTE-FCC option) |
0.1º |
0.1º |
0.1º |
0.1º |
0.1º |
0.1º |
0.1º |
0.1º |
0.1º |
0.1º |